Electricity Use Outside Opening Hours: How to Find Equipment That Runs Overnight for No Reason

Osvětlená okna prázdných kancelářských prostor v noci – typický příklad spotřeby elektřiny mimo provozní dobu, kdy zařízení zbytečně běží přes noc.

At ten in the evening, the office is empty, the retail unit is locked and nobody is working in the warehouse. Yet the electricity meter keeps running. Part of that consumption is fine, because security systems, servers or refrigeration have to operate overnight. Another part, however, comes from equipment nobody needs: lighting that someone forgot to switch off, ventilation with a schedule set to run around the clock, or dozens of devices sitting in standby. If you know how to read night-time consumption, you can find them without major investment.

A monthly electricity bill tells you how much a building used, but not when. Yet the hours when the premises are closed are the most valuable ones for spotting waste. The consumption that remains after the last people leave is called the base load. It is the lowest demand the building never drops below during a day or week, and in many buildings it makes up a surprisingly large share of total consumption, because it runs 24 hours a day, 7 days a week.

Our article Night-Time Water Use was built on the same principle: night-time meter readings reveal running toilets and hidden leaks. With electricity the approach is similar, there are just more consumers, and not every night-time load is a fault. The goal is therefore not to bring night consumption down to zero, but to tell apart what must run overnight, what may run and what should not run at all.

What base load is and why it matters

Think of the base load as the “floor” of the consumption curve. During the day, operations sit on top of it: computers, lighting, the kitchenette, building services and air conditioning. At night and at weekends, demand falls back to it. If the floor is high, the building pays for energy even in hours when it produces nothing, sells nothing and serves no one.

Long-term change matters too. When the base load rises over several weeks, something in the building has changed: new equipment was added, someone switched the ventilation mode, a thermostat failed or a heater was left on. On the bill, such a change disappears in the total, but it is clearly visible in the night-time values.

Where to get the data: from manual readings to 15-minute values

The simplest option is once again a manual test. In the evening, after operations end, write down the meter reading; in the morning, before people arrive, read it again. The difference divided by the number of hours gives the average night-time demand in kilowatts. It is worth repeating the test over several nights and at least once over a weekend, when the premises are closed the longest and the result is least distorted.

Interval data give a more detailed picture. For supply points with interval metering, typically larger connections, the distribution system operator records consumption in short intervals, and the data are usually available in its customer portal. Where no such metering exists, a remotely read sub-meter in the main switchboard or on individual outgoing circuits can help. Hourly or 15-minute values show not only how much the building draws at night, but also when and in what pattern.

If the building already tracks space occupancy, as we described in the article Space Occupancy Data, night-time consumption can be compared with the actual presence of people. Demand at a time when, according to the sensors, nobody is in the building is the clearest signal worth investigating.

What the shape of the night-time curve reveals

The shape of the curve often tells you more than the number itself. A flat, high line all night points to equipment in continuous operation. Regular spikes suggest thermostat-controlled loads such as refrigeration or water heating. Jumps at exactly the same hour are usually time schedules.

EquipmentWhy it runs at nightIs it necessary?What to do
Lighting in offices, corridors and shop windowsForgotten switch-off, no time control, incorrectly set sensorsUsually not, except for emergency and security lightingTime schedule, presence sensors, check of shop-window lighting settings
VentilationSchedule set to continuous operation, manual mode left after servicingOnly where justified (process equipment, storage with environmental requirements)Setback mode outside operating hours, review of time schedules
Heating and coolingNo night setback, heating and cooling running at the same timeSetback yes, full operation usually notNight and weekend temperatures, frost protection kept in place
Electric water heatersContinuous heating regardless of demandDepends on operations, often can be limitedTime switches, check of temperature and hygiene requirements
IT, printers, monitors, coffee machinesStandby mode, workstations left onServers and network yes, the rest mostly notSwitching off socket circuits for office equipment, rules for staff
Refrigeration and freezing equipmentMaintaining temperature continuouslyYesCheck of seals, condition and settings, not switching off

How to find the specific equipment: step by step

Once it is clear that night-time consumption is higher than it should be, it is time to find the culprit. It pays to move from the simplest steps to the more complex ones.

The first step is a night walk-through. Simply go through the building after closing and note what is lit, what is humming, what is warm and what is blinking. Shop-window lighting in retail units often stays on until morning, monitors and printers keep running in offices, and warehouse halls stay lit even where nobody works at night.

The second step is checking time schedules. Control systems for ventilation, heating, cooling and lighting have their own calendars. After servicing, a power outage or a change in opening hours, they are often left in manual mode or with old settings. Comparing the schedules with actual operating hours tends to be the cheapest saving of all.

The third step is measurement at switchboard level. A qualified electrician can measure the load on individual outgoing circuits, for example with a clamp meter, and determine which circuit contributes most to the night-time load. Where operations allow, the load can also be verified by switching off selected circuits in a controlled way while watching the main meter. Such a procedure, however, belongs only to a person with the appropriate professional qualification and precise knowledge of what is connected to which circuit.

Caution: some equipment must run continuously, and switching it off can endanger safety or operations. This includes fire detection and alarm systems, emergency lighting, security and CCTV systems, servers and network equipment, refrigeration of food or medicines, pumps and frost protection. Before any intervention in a switchboard, it must be clear what is connected to the circuit, and up-to-date design documentation of the electrical installation helps a great deal.

From one-off searching to ongoing monitoring

A cause that has been found and removed can come back. That is why it makes sense to turn the night test into a regular indicator. The approach is similar to water: over several weeks you establish the building’s normal night-time level, the baseline, and an alert is raised only when the night-time load exceeds it for several nights in a row. Weekends, public holidays and seasonal changes in heating and cooling are best evaluated separately, otherwise monitoring will be flooded with false alarms.

An alert on its own saves nothing. As we wrote in the article From Monitoring to Control, data only have value once someone or something responds to them. For night-time electricity use, this usually means a clearly assigned person who checks the time schedules or does a walk-through, and a record of the result, so the next alert does not start from scratch.

Checklist: electricity use outside operating hours

☐ Repeated evening and morning readings
Several nights in a row and at least one weekend, converted to average night-time demand.

☐ Interval data
Checked whether they are available in the distribution operator’s portal or from sub-meters.

☐ List of equipment that must run
Fire alarm, emergency lighting, security, servers, refrigeration, frost protection.

☐ Night walk-through
Lighting, shop windows, office equipment, water heaters and humming equipment recorded room by room.

☐ Time schedule check
Ventilation, heating, cooling and lighting match actual operating hours.

☐ Measurement on switchboard circuits
Carried out by a qualified person according to up-to-date electrical documentation.

☐ Rule and responsibility
Baseline, alert threshold and the person who responds to it.

FAQ: Night-time electricity use

What level of night-time consumption is still normal?

There is no universal value. An office with a server room, a shop with refrigerated display cases and a warehouse without technical equipment have completely different base loads. It makes the most sense to compare the building primarily with itself over time and with what must run in it overnight.

Is a manual meter reading enough?

For a first orientation, yes. It shows whether night-time consumption is high. To determine when and in what pattern the building draws power at night, and for ongoing monitoring, hourly or 15-minute data are far more useful.

Can I switch off circuits in the switchboard myself?

Work in a switchboard belongs to a person with the appropriate electrical qualification. There is also a risk of accidentally switching off equipment that must keep running, such as security, refrigeration or the server room. It is safer to start with a walk-through and a check of time schedules and leave circuit measurements to a professional.

What if the building has several tenants?

Then sub-meters for individual units and common areas help. The night-time load can be assigned to a specific part of the building, which shortens the search considerably.

How often should night-time consumption be checked?

With manual readings, a check at least after every change in operating hours, after servicing of building equipment and when switching between the heating and cooling seasons works well. With continuous data, a set rule that flags deviations from the baseline is enough.

Switchboards, circuits and findings in one place

Tracking down night-time consumers is faster when it is clear what is connected where. In the INTECHI Client Portal, every switchboard and sub-meter can have its own device card with its location, the areas it supplies and its history of records. Drawings and schematics taken from CAD documentation can be attached to the cards, so the technician measuring outgoing circuits is not working blind and the measurement results stay with the specific device.

When a night walk-through or measurement reveals a problem, such as a faulty presence sensor or ventilation running continuously, the finding becomes a request linked to the specific device, and its resolution remains traceable. The system also tracks deadlines related to the electrical installation, such as inspections or regular check readings, and sends reminders in good time. Automatic import of data from sub-meters and sensors is being tested in pilot operation; whether and to what extent it is possible for a particular building depends on the metering installed.

How INTECHI handles it

INTECHI provides technical operation, maintenance, electrical installation inspections and its own digital environment under one roof. With night-time electricity use, we start with the simplest steps: we evaluate meter readings or available data, carry out a night walk-through, check the time schedules of building equipment and, where needed, measure the load on individual circuits. Findings, repairs and follow-up steps then stay clearly organised in a single client portal.